Customization: | Available |
---|---|
Application: | Three Phase Transducer, Single-phase Transducer |
Output Type: | 50/60, 400 Hz Optional |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Circuit mode | IGBT/PWM pulse width adjustment mode |
Wire system | 1-phase-3-wire-system |
Input voltage | Phase to Neutral: 154V-286V |
Input frequency | 30-70Hz |
Output voltage | Phase to Neutral: 220V,0~300V |
Output frequency | 50/60Hz, 400Hz optional |
Frequency stability | ≤±0.01% |
Insulation resistance | Above 500Vdc 20MΩ |
Pressure endurance insulation | 1800Vac/5Ma/1minute |
Cooling device | Compulsive fan cooling |
Noise | <55dB |
Wave deformation | ≤2% |
Reaction time | Dynamic response quick, when load 0-100% change, the steady-state response time <20ms |
Efficiency | Efficiency more than 90%, be suit for wide-load, can be for the inductive, capacitive, resistive, and any mixed loads |
Protective device | The importation of non-fuse switch, without output fuse switch, the electronic circuit to detect over-voltage express .Over voltage, over current, over temperature, over load, short circuit, and automatic alarm |
Display | Digital frequency meter, Digital voltage meter, Digital current meter, Digital power/PF meter |
Ambient temperature operating | -10 °C to +50 °C |
Altitude | <1500m |
Relative humidity | <90% |